Smoke extract fans

Certified to hold their duty in 400°C for two hours. Tested by a notified body, not by us, and the certificate travels with the fan.

The range

Smoke extract fans

  • F300, F400 and F600 classifications
  • Certified to EN 12101-3 by a notified body
  • Certificate number on the nameplate
  • Dual-speed for day ventilation and smoke duty
  • Impeller and casing clearances set for thermal growth
  • Control philosophy reviewed free at tender

A smoke extract fan has one job and it happens once. Everything about the specification exists so that the fan is still turning after ninety minutes in air that would have destroyed an ordinary unit in ten — a motor wound with high-temperature insulation, bearings greased for the duty rather than for the shelf, a casing that will not distort enough to jam the impeller as it expands, and cable entries that survive the same.

EN 12101-3 classifies these by temperature and time: F300 is 300°C for 60 minutes, F400 is 400°C for 120, F600 is 600°C for 60. Those ratings are only meaningful when a notified body has watched the test. We hold current certificates for eleven fan and motor combinations, and each nameplate carries the certificate number so a building control officer can check it rather than take it on trust.

The part that goes wrong on site is almost never the fan. It is the wiring, the fire-rated cabling, the damper interlocks and the control panel — and a certified fan on an uncertified installation is not a certified system. We will review your control philosophy at tender stage for nothing, because we would rather do that than be blamed at handover.

Numbers

Envelope

Ranges are the built envelope, not a marketing maximum. Duties near the edge get a measured curve before we quote.

Specification envelope for the Smoke extract fans range
ClassificationsF300 / F400 / F600
Volume range1 – 45 m³/s
Static pressureUp to 1,600 Pa
Certified combinationsEleven, current
Dual speedStandard on axial cases
NameplateCertificate number stamped

Next step

Send us the duty and we will send back a curve

Volume, static pressure, air temperature and what is in it. If you only have two of those, ring us and we will work out the rest.